|
(d)
|
Systems using gas or propane water heaters to serve individual
dwelling units shall include the following components:
|
|
|
1.
|
A dedicated 125 volt, 20 amp electrical receptacle that is connected
to the electric panel with a 120/240 volt 3 conductor, copper branch
circuit rated to 30 amps, within three feet from the water heater
and accessible to the water heater with no obstructions. In addition,
all of the following:
|
|
|
|
A.
|
Both ends of the unused conductor shall be labeled with the
word "spare" and be electrically isolated; and
|
|
|
|
B.
|
A reserved single pole circuit breaker space in the electrical
panel adjacent to the circuit breaker for the branch circuit in A
above and labeled with the words "Future 240V Use";
|
|
|
2.
|
A condensate drain that is no more than two inches higher than
the base of the installed water heater, and allows natural draining
without pump assistance,
|
|
|
3.
|
The construction drawings shall indicate the location of the
future heat pump water heater. The reserved location shall have minimum
interior dimensions of 39"x39"x96"
|
|
|
4.
|
A ventilation method meeting one of the following:
|
|
|
|
A.
|
The location reserved for the future heat pump water heater
shall have a minimum volume of 700 cu. ft.,
|
|
|
|
B.
|
The location reserved for the future heat pump water heater
shall vent to a communicating space in the same pressure boundary
via permanent openings with a minimum total net free area of 250 sq.
in., so that the total combined volume connected via permanent openings
is 700 cu. ft. or larger. The permanent openings shall be:
|
|
|
|
|
i.
|
Fully louvered doors with fixed louvers consisting of a single
layer of fixed flat slats; or
|
|
|
|
|
ii.
|
Two permanent fixed openings, consisting of a single layer of
fixed flat slat louvers or grilles, one commencing within 12 inches
from the top of the enclosure and one commencing within 12 inches
from the bottom of the enclosure.
|
|
|
|
C.
|
The location reserved for the future heat pump water heater
shall include two 8" capped ducts, venting to the building exterior.
|
|
|
|
|
i.
|
All ducts connections and building penetrations shall be sealed.
|
|
|
|
|
ii.
|
Exhaust air ducts and all ducts which cross pressure boundaries
shall be insulated to a minimum insulation level of R-6.
|
|
|
|
|
iii.
|
Airflow from termination points shall be diverted away from
each other.
|
|
(e)
|
Central Heat Pump Water Heater Electric Ready. Central
water heating systems using gas or propane to serve multiple dwelling
units shall include the following:
|
|
|
1.
|
The system input capacity of the gas or propane water heating
system shall be determined as the sum of the input gas or propane
capacity of all water heating devices associated with each gas or
propane water heating system.
|
|
|
2.
|
Space reserved shall include:
|
|
|
|
A.
|
Heat Pump. The minimum space reserved shall include space for
service clearances, air flow clearances, and keep outs and shall meet
one of the following:
|
|
|
|
|
i.
|
If the system input capacity of the gas water heating system
is less than 200,000 BTU per hour, the minimum space reserved for
the heat pump shall be 2.0 square feet per input 10,000 BTU per hour
of the gas or propane water heating system, and the minimum linear
dimension of the space reserved shall be 48 linear inches.
|
|
|
|
|
ii.
|
If the system input capacity of the gas water heating system
is greater than or equal to 200,000 BTU per hour, the minimum space
reserved for the heat pump shall be 3.6 square feet per input 10,000
BTU per hour of the gas or propane water heating system, and the minimum
linear dimension of the space reserved shall be 84 linear inches.
|
|
|
|
|
iii.
|
The space reserved shall be the space required for a heat pump
water heater system that meets the total building hot water demand
as calculated and documented by the responsible person associated
with the project.
|
|
|
|
B.
|
Tanks. The minimum space reserved shall include space for service
clearances and keep outs and shall meet one of the following:
|
|
|
|
|
i.
|
If the system input capacity of the gas water heating system
is less than 200,000 BTU per hour, the minimum space reserved for
the storage and temperature maintenance tanks shall be 4.4 square
feet per input 10,000 BTU per hour, of the gas or propane water heating
system.
|
|
|
|
|
ii.
|
If the system input capacity of the gas water heating system
is greater than or equal to 200,000 BTU per hour, the minimum physical
space reserved for the storage and temperature maintenance tanks shall
be 3.1 square feet per input 10,000 BTU per hour. of the gas or propane
water heating system.
|
|
|
|
|
iii.
|
The space reserved shall be the space required for a heat pump
water heater system that meets the total building hot water demand
as calculated and documented by the responsible person associated
with the project.
|
|
|
3.
|
Ventilation shall be provided by meeting one of the following:
|
|
|
|
A.
|
Physical space reserved for the heat pump shall be located outside,
or
|
|
|
|
B.
|
A pathway shall be reserved for future routing of supply and
exhaust air via ductwork from the reserved heat pump location to an
appropriate outdoor location. Penetrations through the building envelope
for louvers and ducts shall be planned and identified for future use.
The reserved pathway and penetrations through the building envelope
shall be sized to meet one of the following:
|
|
|
|
|
i.
|
If the system input capacity of the gas water heating system
is less than 200,000 BTU per hour, the minimum air flow rate shall
be 70 CFM per input 10,000 BTU per hour of the gas or propane water
heating system and the total external static pressure drop of ductwork
and louvers shall not exceed 0.17 inch when the future heat pump water
heater is installed.
|
|
|
|
|
ii.
|
If the system input capacity of the gas water heating system
is greater than or equal to 200,000 BTU per hour, the minimum air
flow rate shall be 420 CFM per input 10,000 BTU per hour of the gas
or propane water heating system and the total external static pressure
drop of ductwork and louvers shall not exceed 0.17 inch when the future
heat pump water heater is installed.
|
|
|
|
|
iii.
|
The reserved pathway and penetrations shall be sized to serve
a heat pump water heater system that meets the total building hot
water demand as calculated and documented by the responsible person
associated with the project.
|
|
|
4.
|
Condensate drainage piping. An approved receptacle that is sized
in accordance with the California Plumbing Code to receive the condensate
drainage shall be installed within three feet of the reserved heat
pump location, or piping shall be installed from within three feet
of the reserved heat pump location to an approved discharge location
that is sized in accordance with the California Plumbing Code, and
meets one of the following:
|
|
|
|
A.
|
If the system input capacity of the gas water heating system
is less than 200,000 BTU per hour, condensate drainage shall be sized
for 0.2 tons of refrigeration capacity per input 10,000 BTU per hour
|
|
|
|
B.
|
If the system input capacity of the gas water heating system
is greater than or equal to 200,000 BTU per hour, condensate drainage
shall be sized for 0.7 tons of refrigeration capacity per input 10,000
BTU per hour.
|
|
|
|
C.
|
Condensate drainage shall be sized to serve a heat pump water
heater system that meets the total building hot water demand as calculated
and documented by the responsible person associated with the project.
|
|
|
5.
|
Electrical.
|
|
|
|
A.
|
Physical space shall be reserved on the bus system of the main
switchboard or on the bus system of a distribution board to serve
the future heat pump water heater system including the heat pump and
temperature maintenance tanks. In addition, the physical space reserved
shall be capable of providing adequate power to the future heat pump
water heater as follows:
|
|
|
|
|
i.
|
Heat Pump. For the Heat Pump, the physical space reserved shall
comply with one of the following:
|
|
|
|
|
|
A.
|
If the system input capacity of the gas water heating system
is less than 200,000 BTU per hour, provide 0.1 kVA per input 10,000
BTU per hour
|
|
|
|
|
|
B.
|
If the system input capacity of the gas water heating system
is greater than or equal to 200,000 BTU per hour, provide 1.1 kVA
per input 10,000 BTU per hour
|
|
|
|
|
|
C.
|
The physical space reserved supplies sufficient electrical power
required to power a heat pump water heater system that meets the total
building hot water demand as calculated and documented by the responsible
person associated with the project.
|
|
|
|
|
ii.
|
Temperature Maintenance Tank. For the Temperature Maintenance
Tank, the physical space reserved shall comply with one of the following:
|
|
|
|
|
|
A.
|
If the system input capacity of the gas water heating system
is less than 200,000 BTU per hour, provide 1.0 kVA per input 10,000
BTU per hour
|
|
|
|
|
|
B.
|
If the system input capacity of the gas water heating system
is greater than or equal to 200,000 BTU per hour, provide 0.6 kVA
per input 10,000 BTU per hour
|
|
|
|
|
|
C.
|
The physical space reserved supplies sufficient electrical power
required to power a heat pump water heater system that meets the total
building hot water demand as calculated and documented by the responsible
person aIssociated with the project.
|
|
(f)
|
The building electrical system shall be sized to meet the future
electric requirements of the electric ready equipment specified in
sections 160.9 a — e. To meet this requirement the building
main service conduit, the electrical system to the point specified
in each subsection, and any on-site distribution transformers shall
have sufficient capacity to supply full rated amperage at each electric
ready appliance in accordance with the California Electric Code.
|