Definitions used in this chapter, unless the context requires
otherwise, are as follows:
"Air gap separation - approved"
means a physical break between the supply pipe and a receiving
vessel. The air gap shall be at least double the diameter of the supply
pipe, measured vertically above the top rim of the receiving vessel,
and in no case less than one inch.
"Backflow"
refers to the flow of water or other fluid or substance or
combination or mixture thereof into the potable water supply distribution
pipes from any source or sources other than the intended source of
supply.
"Check valve - approved"
means a check valve that is drip-tight in the normal direction
of flow when the inlet pressure is at least one psi and the outlet
pressure is zero. The check valve shall permit no leakage in a direction
reverse to the normal flow. The closure element (e.g. clapper, poppet
and other design) shall be internally weighted or otherwise internally
loaded to promote rapid and positive closure. An approved check valve
is only one component of an approved backflow prevention assembly,
i.e., pressure vacuum breaker, double check valve assembly or reduced
pressure principle assembly.
"Cross-connection"
means any unprotected actual or potential connection or structural
arrangement between a public or a consumer's potable water system
and any other source or system through which it is possible to introduce
into any part of the potable system any used water, industrial fluid,
gas, or substance other than the intended potable water with which
the system is supplied. Bypass arrangements, jumper connections, removable
sections, swivel or change over devices and other temporary or permanent
devices through which or because of which backflow can or may occur
are cross-connections.
"Double check valve assembly - approved"
means an assembly composed of two single, independently acting,
approved check valves, including tightly closing shut-off valves located
at each end of the assembly and fitted with properly located test
cocks.
"Reclaimed water"
means wastewater which as a result of tertiary treatment
is suitable for uses other than potable use.
"Reduced pressure principle backflow prevent assembly - approved"
means a device containing two independently acting approved
check valves, together with a hydraulically operating, mechanically
independent pressure relief valve located between the check valves
and at the same time below the first check valve. The unit shall include
properly located test cocks and tightly closing shutoff valves at
each end of the assembly.
"Service connection"
means the terminal end of a service connection from the public
potable water system, i.e., where the water purveyor loses jurisdiction
and sanitary control over the water at its point of delivery to the
consumer's water system. If a meter is installed at the end of the
service connection, then the service connection shall mean the downstream
end of the meter.
(Ord. 236 §1, 1983; Ord. 314 §2, 1990)