Section 5.106.5.3 of the 2022 California Green Building Code
and its subsections are amended to read as follows:
5.106.5.3 Electric vehicle (EV) charging. Construction
shall comply with Section A5.106.5.3.1 Tier 1, and in accordance with
regulations in the
California Building Code and the California Electrical
Code.
A5.106.5.3.1 Tier 1. Comply with Section 5.106.5.3.1
EV capable spaces, Section 5.106.5.3.2 Electric vehicle charging stations
and associated Table A5.106.5.3.1 Tier 1, or comply with Section A5.106.5.3.2
Electric vehicle charging stations (EVCS) — Power
allocation method and associated Table A5.106.5.3.2 Tier 1.
Refer to Section 5.106.5.3.2 for the permitted use of Level
2 or direct current fast charger (DCFC) to create EVCS. Refer to Section
5.106.3.2.1 for the allowed use of DCFC to comply with both EV capable
spaces and Level 2 EVSE. Refer to Section 5.106.5.3.3 for the allowed
use of automatic load management system (ALMS).
|
Table A5.106.5.3.1
|
|---|
|
Total Number of Actual Parking Spaces
|
Tier 1 Number of Required EV Capable Spaces
|
Tier 1 Number of EVCS (EV Capable Spaces Provided with EVSE)2
|
|---|
|
0-9
|
2
|
0
|
|
10-25
|
5
|
2
|
|
26-50
|
11
|
4
|
|
51-75
|
19
|
5
|
|
76-100
|
26
|
9
|
|
101-150
|
38
|
13
|
|
151-200
|
53
|
18
|
|
201 and over
|
30% of actual parking spaces1
|
33% of EV capable spaces1
|
|
Notes:
|
|
1. Calculation for spaces shall be rounded up to the nearest
whole number.
|
|
2. The number of required EVCS (EV capable spaces provided with
EVSE) in column 3 count toward the total number of required EV capable
spaces shown in column 2.
|
|
3. At least one Level 2 EVSE shall be provided.
|
A5.106.5.3.2 Electric vehicle charging stations (EVCS)
- Power Allocation method. The power allocation method may
be used as an alternative to the requirements in Section 5.106.5.3.1,
Section 5.106.5.3.2, and associated Table A5.106.5.3.1 Tier 1. Use
Table A5.106.5.3.2 Tier 1 to determine the total power in kVA required
based on the total number of actual parking spaces.
|
Power allocation method shall include the following:
|
|
1.
|
Use any kVA combination of EV capable spaces, low power Level
2, Level 2 or DCFC EVSEs.
|
|
2.
|
At least one Level 2 EVSE shall be provided.
|
|
Table A5.106.5.3.2 Tier 1
|
|---|
|
Total Number of Actual Parking Spaces
|
Minimum Total kVA@ 6.6 kVA
|
Total kVA Required in any Combination of EV Capable3, 4, Low Power Level 2, Level 21, 2, or DCFC
|
|---|
|
0-9
|
13.2
|
13.2
|
|
10-25
|
33
|
33
|
|
26-50
|
72.6
|
72.6
|
|
51-75
|
125.4
|
125.4
|
|
76-100
|
171.6
|
171.6
|
|
101-150
|
250.8
|
250.8
|
|
151-200
|
349.8
|
349.8
|
|
201 and over
|
30% of actual parking spaces x 6.6
|
Total required kVA = P x 0.30 x 6.6
Where P = Parking spaces in facility
|
|
Notes:
|
|
1.
|
Level 2 EVSE at 6.6 kVA minimum.
|
|
2.
|
At least one Level 2 EVSE shall be provided.
|
|
3.
|
Maximum allowed kVA to be utilized for EV capable spaces is
67%.
|
|
4.
|
If EV capable spaces are utilized, they shall meet the requirements
of Section 5.106.5.3.1 EV capable spaces.
|
5.106.5.3.3 Use of automatic load management systems (ALMS). ALMS shall be permitted for EVCS. When an ALMS is installed, the
required electrical load capacity specified in Section 5.106.5.3.1
for each EVCS may be reduced when serviced by an EVSE controlled by
an ALMS. Each EVSE controlled by an ALMS shall deliver a minimum 30
amperes to an EV when charging one vehicle and shall deliver a minimum
3.3 kW while simultaneously charging multiple EVs.
5.106.5.3.4 Accessible electric vehicle charging station
(EVCS). When EVSE is installed, accessible EVCS shall be provided
in accordance with the
California Building Code Chapter 11B, Section
11B-228.3.
Note: 5.106.5.3.5 Electric
vehicle charging station signage. For EVCS
signs, refer to Electric vehicle charging stations
shall be identified by signage or pavement markings in compliance
with Caltrans Traffic Operations Policy Directive 13-01 (Zero Emission
Vehicle Signs and Pavement Markings) or its successor(s).
5.106.5.3.5.1 Additional EV ready requirement for office
facilities. In addition to the requirements of Table A5.106.5.3.1,
for office parking facilities, an additional 20% (rounded to the nearest
whole number) of the total number of parking spaces shall be equipped
with low power Level 2 EV charging receptacles.
5.106.5.4 Additions or alterations to existing buildings
or parking facilities [A]. [BSC-CG] Existing buildings or parking
facilities being modified by one of the following shall comply with
Section 5.106.5.4.1 or 5.106.5.4.2. When EVSE is installed, accessible
EVCS shall be provided in accordance with the California Building
Code, Chapter 11B, Section 11B-228.3.
|
1. When the scope of construction work includes
an increase in power supply to an electric service panel as part of
a parking facility addition or alteration.
|
|
2. When a new photovoltaic system is installed covering
existing parking spaces.
|
|
3. When additions or alterations to existing buildings
are triggered pursuant to code Section 301.3 and the scope of work
includes an increase in power supply to an electric service panel.
|
|
Exceptions:
|
|
1. On a case-by-case basis where the local enforcing
agency has determined compliance with this Section is not feasible
based upon one of the following conditions:
|
|
a. Where there is no local utility power supply.
|
|
b. Where the local utility is unable to supply adequate
power.
|
|
c. Where there is evidence suitable to the local
enforcement agency substantiating that additional local utility infrastructure
design requirements, directly related to the implementation of Section
5.106.5.3, may adversely impact the construction cost of the project.
|
|
d. Where demonstrated as impracticable excluding
local utility service or utility infrastructure issues.
|
|
2. Remote parking facilities that do not have access
to the building service panel.
|
|
3. Parking area lighting upgrades where no trenching
is part of the scope of work.
|
|
4. Emergency repairs, including, but not limited
to, water line break in parking facilities, natural disaster repairs,
etc.
|
5.106.5.4.1 Existing buildings or parking areas without
previously installed EV capable infrastructure [A]. When EV
capable infrastructure does not exist at an existing parking facility
or building, and the parking facility or building undergoes an addition
or alteration listed in Section 5.106.5.4, construction shall include
electric vehicle charging in compliance with either Section 5.106.5.3
and associated Table 5.106.5.3.1, or Section 5.106.5.3.6 and associated
Table 5.106.5.3.6 for the total number of actual parking spaces being
added or altered.
5.106.5.4.2 Existing buildings or parking areas with previously
installed EV capable infrastructure [A]. When EV capable infrastructure
is available at an existing parking facility or building, and the
parking facility or building is undergoing an addition or alteration
listed in Section 5.106.5.4, construction shall include electric vehicle
charging in compliance with either Section 5.106.5.3 and associated
Table 5.106.5.3.1, or Section 5.106.5.3.6 and associated Table 5.106.5.3.6
utilizing the existing EV capable allocated power and infrastructure
for the total number of actual parking spaces being added or altered.
If the area being added or altered exceeds the existing EV capable
capacity, allocated power and infrastructure, provide additional EV
charging as needed to comply with this section.
5.106.5.5 Electric vehicle (EV) charging: medium-duty
and heavy-duty. [N] [BSG-CG] Construction shall comply with
Section 5.106.5.4.1 to facilitate future installation of electric
vehicle supply equipment (EVSE). Construction for warehouses, grocery
stores and retail stores with planned off-street loading spaces shall
also comply with Section 5.106.5.4.5.1 for future installation of
medium- and heavy-duty EVSE.
|
Exceptions:
|
|
1.
|
On a case-by-case basis where the local enforcing agency has
determined compliance with this section is not feasible based upon
one of the following conditions:
|
|
|
a.
|
Where there is no local utility power supply.
|
|
|
b.
|
Where the local utility is unable to supply adequate power.
|
|
|
c.
|
Where there is evidence suitable to the local enforcing agency
substantiating that additional local utility infrastructure design
requirements, directly related to the implementation of Section 5.106.5.3,
may adversely impact the construction cost of the project.
|
When EVSE(s) is/are installed, it shall be in accordance with
the
California Building Code, the California Electrical Code and as
follows:
5.106.5.4.5.1 Electric vehicle charging readiness requirements
for warehouses, grocery stores and retail stores with planned off-street
loading spaces. In order to avoid future demolition when adding
EV supply and distribution equipment, spare raceway(s) or busway(s)
and adequate capacity for transformer(s), service panel(s) or subpanel(s)
shall be installed at the time of construction in accordance with
the California Electrical Code. Construction plans and specifications
shall include, but are not limited to, the following:
|
1.
|
The transformer, main service equipment and subpanels shall
meet the minimum power requirement in Table 5.106.5.5.1 to accommodate
the dedicated branch circuits for the future installation of EVSE.
|
|
2.
|
The construction documents shall indicate one or more location(s)
convenient to the planned off-street loading space(s) reserved for
medium- and heavy-duty ZEV charging cabinets and charging dispensers,
and a pathway reserved for routing of conduit from the termination
of the raceway(s) or busway(s) to the charging cabinet(s) and dispenser(s),
as shown in Table 5.106.5.5.1.
|
|
3.
|
Raceway(s) or busway(s) originating at a main service panel
or a subpanel(s) serving the area where potential future medium- and
heavy-duty EVSE will be located, and shall terminate in close proximity
to the potential future location of the charging equipment for medium-
and heavy-duty vehicles.
|
|
4.
|
The raceway(s) or busway(s) shall be of sufficient size to carry
the minimum additional system load to the future location of the charging
for medium- and heavy-duty ZEVs as shown in Table 5.106.5.4.5.1.
|
|
Table 5.106.5.4.5.1
Raceway Conduit and Panel Power Requirements for Medium- and
Heavy-Duty EVSE [N]
|
|---|
|
Building Type
|
Building Size
(sq. ft.)
|
Number of Off-Street Loading Spaces
|
Additional Capacity Required (kVa) for Raceway & Busway
and Transformer & Panel
|
|---|
|
Grocery
|
|
1 or 2
|
200
|
|
10,000 to 90,000
|
3 or Greater
|
400
|
|
Greater than 90,000
|
1 or Greater
|
400
|
|
Manufacturing Facilities
|
10,000 to 50,000
|
1 or 2
|
200
|
|
10,000 to 50,000
|
3 or Greater
|
400
|
|
Greater than 50,000
|
1 or Greater
|
400
|
|
Office Buildings
|
10,000 to 135,000
|
1 or 2
|
200
|
|
10,000 to 135,000
|
3 or Greater
|
400
|
|
Greater than 135,000
|
1 or Greater
|
400
|
|
Retail
|
10,000 to 135,000
|
1 or 2
|
200
|
|
3 or Greater
|
400
|
|
Greater than 135,000
|
1 or Greater
|
400
|
|
Warehouse
|
20,000 to 256,000
|
1 or 2
|
200
|
|
3 or Greater
|
400
|
|
Greater than 256,000
|
1 or Greater
|
400
|
5.106.5.6 Electric vehicle (EV) charging at public schools
and community colleges. [DSA-SS] Electric vehicle infrastructure
and electric vehicle charging stations shall comply with Section 5.106.5.6
and shall be provided in accordance with regulations in the California
Building Code and the California Electrical Code.
|
Exceptions:
|
|
1. On a case-by-case basis where compliance with
this Section has been demonstrated to be not feasible based upon one
of the following conditions, and with concurrence by the Division
of the State Architect (DSA), compliance with Section 5.106.5.6 shall
not be required.
|
|
|
a.
|
Where there is no local utility power supply.
|
|
|
b.
|
Where the local utility is unable to supply adequate power.
|
|
|
c.
|
The installation of EVCS is impracticable.
|
|
2. Parking spaces accessible only by automated mechanical
car parking systems are not required to comply with Section 5.106.5.6.
|
|
5.106.5.6.1 EV capable spaces. EV capable spaces
shall be provided in accordance with Table A5.106.5.6.1 and the following
requirements:
|
|
1. Raceways complying with the California Electrical
Code and no less than one-inch (25 mm) diameter shall be provided
and shall originate at a service panel or a subpanel(s) serving the
area and shall terminate in close proximity to the proposed location
of the EV capable space and into a suitable listed cabinet, box, enclosure
or equivalent. A common raceway may be used to serve multiple EV capable
spaces.
|
|
2. A service panel or subpanel(s) shall be provided
with panel space and electrical load capacity for a dedicated 208/240
volt, 40-ampere minimum branch circuit for each EV capable space,
with delivery of 30-ampere minimum to an installed EVSE at each EVCS.
|
|
3. The electrical system and any on-site distribution
transformers shall have sufficient capacity to supply full rated amperage
at each EV capable space.
|
|
4. The service panel or subpanel circuit directory
shall identify the reserved overcurrent protective device space(s)
as "EV CAPABLE." The raceway termination location shall be permanently
and visibly marked as "EV CAPABLE."
|
5.106.5.6.2 Electric vehicle charging stations (EVCS). EV capable spaces shall be provided with EVSE to create EVCS in
the number indicated in Table 5.106.5.6.1 and shall comply with Section
5.106.5.6.2. EVCS shall be serviced by Level 2 or Direct Current Fast
Charging (DCFC) EVSE, or with EVSE in any combination of Level 2 and
DCFC. Accessible EVCS shall be provided in accordance with California
Building Code Chapter 11B.
5.106.5.6.2.1 Reduced number of EV capable spaces. The installation of each DCFC EVSE shall be permitted to reduce
the minimum number of required EV capable spaces indicated in Table
5.106.5.6.1 by five and reduce proportionally the required electrical
load capacity to the service panel or subpanel.
5.106.5.6.2.2 Multiple connectors. EVSE with multiple
vehicle connectors capable of charging multiple EVs simultaneously
shall be permitted if the electrical load capacity required by Section
5.106.5.6.1 for each EV capable space is accumulatively supplied to
the EVSE.
5.106.5.6.2.3 Use of automatic load management systems
(ALMS). ALMS shall be permitted for EVCS installed in accordance
with Section 5.106.5.6.2. When ALMS is installed, the required electrical
load capacity specified in Section 5.106.5.6.1 for each EVCS may be
reduced when serviced by an EVSE controlled by an ALMS. Each EVSE
controlled by an ALMS shall deliver a minimum 30 amperes to an EV
when charging one vehicle and shall deliver a minimum 3.3 kW while
simultaneously charging multiple EVs.
5.106.5.6.3 EVCS alternative compliance.
In lieu of compliance with Section 5.106.5.6.2, EVCS shall be
provided with Level 1, low power Level 2, or Level 2, or any combination
of Level 1, low power Level 2 or Level 2 EVSE such that the total
power supplied by the combination of EVSE meets the minimum power
indicated in Table 5.106.5.6.3, based on the total number of actual
parking spaces in each parking facility.
|
Table 5.106.5.6.3
|
|---|
|
Number of Parking Spaces in a Parking Facility
|
Minimum Total Power (kVa) Required for EVCS
|
|---|
|
0-9
|
0
|
|
10-25
|
7
|
|
26-50
|
14
|
|
51-75
|
20
|
|
76-100
|
27
|
|
101-150
|
40
|
|
151-200
|
60
|
|
201 and over
|
Total required KVA = P x 0.05 x 6.6
Where P = Parking spaces in facility
|
5.106.5.6.4 EVCS for alterations of or additions to parking
facilities. Alterations of or additions to parking facilities
shall provide EVCS in compliance with Section 5.106.5.6.4. The installation
of infrastructure for EV capable spaces required to be provided without
EVSE shall not be required.
5.106.5.6.4.1 Alterations of and additions to parking
facilities. EVCS shall be provided in accordance with the number
indicated in Table 5.106.5.6.1 or minimum power indicated in Table
5.106.5.6.3 when the scope of work includes an increase in power supply
to an electric panel serving light fixtures illuminating the parking
area or when area containing parking spaces is added to a parking
facility. The number of required EVCS shall be based on the total
number of existing and new parking spaces in the parking facility.
5.106.5.6.4.2 Alterations consisting of the installation
of photovoltaic systems. EVCS shall be provided in accordance
with the number indicated in Table 5.106.5.6.1 or maximum power indicated
in Table 5.106.5.6.3 when a new photovoltaic system is installed in
an existing parking facility.
5.106.5.6.5 Requirement to install EVSE. Level
2 EVSE shall be provided in all existing EV capable spaces to create
EVCS when a project is required by
California Administrative Code
Section 4-309 to be submitted for plan approval to the Division of
the State Architect. When EVSE is installed in existing EV capable
spaces, accessible EVCS shall be provided in accordance with California
Building Code Chapter 11B.
Exception: Projects in which improvements in parking
areas consist only of accessibility improvements are not required
to comply with Section 5.106.5.6.5.
(Added by Ord. No. 2634CCS §
3, adopted 4/28/20; amended by Ord. No. 2723CCS § 4, adopted 10/11/22; Ord. No. 2783CCS, 6/25/2024)